| WALL ASSEMBLY COMPONENTS1 |
RSI |
R |
| 1 |
exterior air film |
0.03 |
0.17 |
| 2 |
vinyl siding |
0.00 |
0.00 |
| 3 |
more than 3/4" (20mm +) air space |
0.00 |
0.00 |
| 4 |
2" (50.8mm) rock fibre semi rigid board |
1.41 |
7.99 |
| 5 |
spun bonded polyolefin (house wrap) |
0.00 |
0.00 |
| 6 |
1/2" (12.7mm) Plywood sheathing |
0.11 |
0.62 |
| 7 |
2x6 framing filled with R22 batt @ 16" o.c. |
2.55 |
14.48 |
| 8 |
polyethylene |
0.00 |
0.00 |
| 9 |
1/2" (12.7mm) gypsum board |
0.08 |
0.45 |
| 10 |
finish: 1 coat latex primer and latex paint |
0.00 |
0.00 |
| 11 |
interior air film |
0.12 |
0.68 |
| Effective RSI / R Value of Entire Assembly |
4.30 |
24.39 |
| Centre of Cavity RSI / R Value |
5.62 |
31.91 |
| Installed Insulation RSI / R Value(nominal) |
5.28 |
29.99 |
Effective RSI / R Value of Assembly with Advanced Framing
(advanced framing as defined by NBC9.36.2.4.(1))
|
4.42 |
25.07 |
Note: 1Values are for generic insulation products. Where a specific insulation product is used in the assembly, the thermal resistance value, or long term thermal resistance value, where applicable, of that product is permitted to be used as reported by the Canadian Construction Materials Centre (CCMC) in the evaluation of such a product.
Summary
- This is a very durable wall overall in all the climate zones listed, due to both the rain screen properties of the vinyl siding combined with the benefits of the insulative sheathing. The vinyl siding is non-absorptive to moisture, thus avoiding solar-driven moisture issues, while maintaining good drying potential towards the outside due to the "air-leakiness" of the siding should any moisture find its way behind it. The house wrap and insulative sheathing behind it act as secondary drainage planes behind the vinyl siding, and also reduces the risk of interstitial condensation by raising the temperature of the wall assembly inboard of it while at the same time maintaining excellent drying capability towards the outside.
Energy & Thermal Performance
- Advanced framing as defined by NBC 9.36.2.4. (1) (e.g. insulated headers, 2 stud corners, ladder blocking, and in-line framing) can potentially reduce the framing factor by 10% to 20%)
- Maximum nominal R-value of cavity insulation is typically limited to R19,20,22,24 (fiberglass batt) to R30 with medium density spray-applied insulation
- Continuous exterior Insulation significantly minimizes thermal bridging and enhances overall effective R-value of the entire assembly

Exterior Moisture/Wetting
- Any liquid water leaking past the vinyl siding will be intercepted by the semi-rigid rock wool wall insulation and drained downwards, or by the spunbonded polyolefin lapped at joints and over a flashing at the bottom of the wall assembly, which both act as a secondary drainage planes and will drain any liquid water to the outside
- The vinyl siding is non-absorptive and rain shedding
- Any moisture which may leak into the wall through penetrations can dry to the outside due to the "air-leakiness" of the vinyl siding, and the excellent drying characteristics of the whole assembly
- The outward drying potential of this wall is greatly reduced by the layer of insulative sheathing, and if a polyethylene vapour retarder is used, it cannot dry to the inside either, so extra care must be taken at all penetrations and transitions (windows etc.) so water does not leak in behind the asphalt impregnated paper and the insulative sheathing, and also that built-in construction moisture is managed to reasonable levels.

Air Leakage Transported Moisture from Inside
- The effect of the semi-rigid rock wool wall insulation is a reduced risk of interstitial condensation on the wood sheathing or in the stud cavity from warm moisture-laden interior air leaking into the wall assembly, as the dew point in the heating season will mostly fall outboard of the wood sheathing and the spunbonded polyolefin
- For colder climates, the thickness of the insulative sheathing should be increased to maintain the location of the dew point falling outside of the wood sheathing
- Air leakage into the wall must be managed by means of a continuous interior or exterior air barrier (preferably both), combined with proper detailing at any connection or penetrations (window openings, electrical boxes, plumbing penetrations etc.), which will also help reduce heating and air conditioning costs
- Should any moisture get into the assembly, it has excellent drying potential towards the outside due to the "air-leakiness" or "breathability" of the vinyl siding, and the very high vapour permeance of the 2" layer of semi-rigid rock wool wall insulation

Water Vapour Diffusion from Outside
- Solar driven moisture is not an issue with vinyl siding and other similar non-absorptive and rain-shedding sidings

Water Vapour Diffusion from Inside
- Vapour diffusion from the inside must be controlled by the installation of a vapour retarding membrane (polyethylene or vapour retarder paint or variable permeance “smart” vapour retarder if the code allows) on the inside behind the gypsum board or painted onto the gypsum board according to code

Ease of Construction
- This wall is easily constructed through traditional stick frame methods on-site
- Exterior wood sheathing provides both structural resistance to "racking" and a nailing substrate for cladding materials
- Insulation, weather barrier and air barrier details and materials are readily available and understood within the Canadian industry
- Constructing walls with exterior insulation is rapidly becoming common practice in some Canadian Zones
- Materials such as studs, wood sheathing panels and/or insulation sheet goods are readily available in pre-cut lengths for 8' and 9' wall heights
- Length of fastener may need minor adjustment to ensure proper penetration depth into framing member
- Due to the semi-rigid nature of the exterior rock wool wall insulation, strapping may be required in order to attach exterior cladding materials (e.g. vinyl or shiplap type siding)

Affordability: Cost Implications
- Reduction in wood use framing stud members possible (19.2" OR 24" o.c.) with no additional engineering required.
- Alternative bracing methods can be substituted for the wood sheathing panel (e.g. T-slot inlet bracing) - however, details for wall bracing, tall walls, and more than 3-storey construction may require additional engineering
- Wall thickness adjustment could require minor increase of foundation wall thickness (e.g. 8" to 10" foundation width) and increase costs
- Wall thickness adjustment could require minor jamb extensions or additional trim details on openings in the enclosure (i.e. for windows and doors)
- Thickness of exterior rigid insulation that is 2" or more may require strapping for adequate fastening of exterior cladding and increase costs
- Advanced framing as defined by NBC 9.36.2.4. (1) (e.g. insulated headers, 2 stud corners, ladder blocking, and in-line framing) can potentially reduce overall lumber costs by upwards of 10 to 20% (i.e. for softwood and panel products)

Esthetics: Architectural Design
- This wall assembly design can be used up to 3 storey construction under most prevailing building codes
- Exterior wood sheathing provides a nailing substrate for cladding materials including various siding applications (vertical or horizontal)
- Wall thickness adjustment could require minor increase of foundation wall thickness (e.g. 8" to 10" foundation width) and increase costs
- Wall thickness adjustment could require minor jamb extensions or additional trim details on openings in the enclosure (i.e. for windows and doors)
- Exterior wall dimension width may have minor effect on interior dimensions (i.e. stair widths on exterior walls and overall interior useable square footage)
Additional Sources of Information
DISCLAIMER:
The Canadian Wood Council's Wall Thermal Design Calculator has been developed for information purposes only. Although all possible efforts have been made to ensure that the information on this tool is accurate, the CWC cannot under any circumstances guarantee the completeness, accuracy or exactness of the information. Reference should always be made to the appropriate Building Code and/or Standard. This tool should not be relied upon as a substitute for legal or design advice, and the user is responsible for how the tool is used or applied.
Although all possible efforts have been made to ensure that the information on this tool is accurate, we cannot under any circumstances guarantee the completeness, accuracy or exactness of the information. Suggestions regarding this tool are welcome. If you feel that areas are missing, unclear or incorrect, please forward your suggestions to wtd@cwc.ca